montblanc: config: Update configuration of COME 2nd source sensors to FBOSS Sensor Config #447
Add this suggestion to a batch that can be applied as a single commit.
This suggestion is invalid because no changes were made to the code.
Suggestions cannot be applied while the pull request is closed.
Suggestions cannot be applied while viewing a subset of changes.
Only one suggestion per line can be applied in a batch.
Add this suggestion to a batch that can be applied as a single commit.
Applying suggestions on deleted lines is not supported.
You must change the existing code in this line in order to create a valid suggestion.
Outdated suggestions cannot be applied.
This suggestion has been applied or marked resolved.
Suggestions cannot be applied from pending reviews.
Suggestions cannot be applied on multi-line comments.
Suggestions cannot be applied while the pull request is queued to merge.
Suggestion cannot be applied right now. Please check back later.
Description
This PR is about updating the configuration of Minipack3 COME 2nd source sensors to FBOSS Sensor's configurations
Motivation
The sensor service hw test failed on Minipack3 devices equipped with the 2nd source COME due to an unsuitable configuration in the Montblanc sensor service config file.
In this PR, the configuration for the 2nd source COME sensors will be reverted to the original version, which is correct and functional.
Test Plan
The correctness of the format has been verified on this jsonlint website.
Verified the updated configurations on the Minipack 3 machine configured with 2nd source COME:
Test log as follows:

1.There was a sensor discovery failure on the 2nd source COME device prior to updating the sensor configuration:
2.Sensor_service run successfully on the 2nd source COME device after updating the sensor configuration:

Minipack3_2nd_COMe_sensor_service_log-BeforeAndAfter.txt
Minipack3_main_COMe_sensor_service_log.txt